Cadence Palladium 帕拉丁 Z1/2 部署实施物理环境需求

最佳实践 0 1858 佚名 收藏
Palladium Z1
Size
    尺寸
Width/宽   Depth/深Height/高
24"38"84"
61 cm97   cm214   cm










Weight/重量2045 lbs / 927.5 Kg  (GXL/水冷机型 3 Cluster)
1725   lbs / 782.5 Kg     (XL/风冷机型 2 Cluster)


Power
    供电
Voltage/电压Amperage/电流Type/类型Circuit   Breaker/空开
380-415 Vac 32A5   Wire,3 Phase (wye) 3P+N+E3 pole x 40A with   delay
Power   Per Rack/单机柜功率: 30.5 KW [XL] / 43KW [GXL] 


Temperature
    温度
Operating/工作: XL:10-20℃
Operating/工作: GXL:10-25   °C
Storage/存储:   1-65℃





Humidity/湿度10-70%  (non-condensing/无冷凝)





Heat Dissipation
    散热
System
    系统
Z1   XL A/C Load
    Z1 XL 风冷负载
Z1   GXL A/C Load
    Z1 GXL 风冷负载
Z1   GXL House
    Water Load
    Z1 GXL 水冷负载
1-Rack/单机柜30.5 KW8.3 KW 34.5 KW





House Water
    Cooling
    水冷
House   Water Temperature
    冷却水温度
Flow   Rate(Min.)
    最小流量

10°C   (Abs. min./最小)17 LPM
15°C   (Recommended/推荐)28 LPM
22°C   (Abs. max.最大)44 LPM





House Water
    Pressure
    冷却水压力
Minimum/最小 = 20 psi

Maximum/最大   = 50 psi






Gap betwwen Racks
    机柜间间距
Keep   100mm space between racks
    建议机柜间保留10公分的间距





Service Area
    安装维护空间
1m in   front, 1m behind
    机柜前后各留1米





pressure drop
    压降
 between the house water supplyline and   return line maximum 16.5 psi.
    供水端与回水端最大压降16.5 psi




Palladium Z2
Size
    尺寸
Width/宽   Depth/深Height/高
28”42”84”
71 cm 107 cm214 cm










Weight/重量2400 lbs / 1090kg  (GXL/水冷机型 3 Cluster)
2030   lbs / 919 Kg     (XL/风冷机型 2 Cluster)





Power
    供电
Voltage/电压Amperage/电流Type/类型Circuit   Breaker/空开
380-415 Vac 40A5   Wire,3 Phase (wye) 3P+N+E3 pole x 40A with   delay
Power   Per Rack/单机柜功率: 35.6 KW [XL] / 50KW [GXL] 





Temperature
    温度
Operating/工作: XL:   10-20°C  18°C  Recommended
GXL: 10-25°C
Storage/存储:   1-65℃





Humidity/湿度10-70% (non-condensing/无冷凝)





Heat Dissipation
    散热
System
    系统
Z2   XL A/C Load
    Z2 XL 风冷负载
Z2   GXL A/C Load
    Z2 GXL 风冷负载
Z2   GXL House
    Water Load
    Z2 GXL 水冷负载
1-Rack35.6 KW7.8 KW42.3 KW





House Water
    Cooling
    水冷
House   Water Temperature
    冷却水温度
Flow   Rate
    流量

10°C21 LPM
15°C  (Recommended/推荐)34 LPM
22   °C54 LPM





House Water
    Pressure
    冷却水压力
Minimum/最小 = 20 psi

Maximum/最大   = 50 psi






Gap betwwen Racks
    机柜间间距
No   space between racks: optical cables are routed within the racks
    机柜间无需保留间距,连接光纤线在机柜内部走线





Service Area
    安装维护空间
1m in   front, 1m behind
    机柜前后各留1米





pressure drop
    压降
 between the house water supplyline and   return line maximum 16.5 psi.
    供水端与回水端最大压降16.5 psi